Introduction
1.6 Screw-Terminal Serial Connectors
Table 2 - Serial Screw-Terminal Pinouts
Pin Direction Name Function
1 To XPress DR
RXD or RXA
RS-232: RXD (Received Data)
RS-422/485:RXA (Received Data -)
4 From XPress DR TXD or TXA RS-232: TXD (Transmit Data)
RS-422/485: TXA (Transmit Data -)
2 To XPress DR CTS or RXB RS-232: CTS (Clear to Send)
RS-422/485: RXB (Received Data +)
3 From XPress DR RTS or TXB RS-232: RTS (Request to Send)
RS-422/485: TXB (Transmit Data +)
8 Ground GND Ground
RXD
C
T
S
RT
S
TXD
Rx- Rx+ Tx+ Tx-
GND
1234
8
Data+ Data-
GND
12 3 4
8
R
R = 120 Ohm, 1/8 W
RxD-
12 34
8
R
R = 120 Ohm, 1/8 W
RS-485 2-Wire RS-422/485 4-Wire
R
RxD+ TxD-TxD+ GND
Note: For RS-485 2-wire functionality, pins 1 & 4 and 2 & 3 of the screw terminals must be
connected together.
Note: Termination resistors (R = 120 Ohm) are used to match impedance of a node to the
impedance of the transmission (TX) line. Termination resistors should be placed only at the
extreme ends of the data line, and no more than two terminations should be placed in any
single segment of a RS-485 network. The terminator resistors may not be needed for your
application.
DSTni-XPress DR User Guide 1-7